Journal of Siberian Federal University. Engineering & Technologies / Electromagnetic Compatibility Issues on Power Systems in the Petroleum Industry

Full text (.pdf)
Issue
Journal of Siberian Federal University. Engineering & Technologies. 2014 7 (6)
Authors
Egorov, Denis E.; Dovgun, Valery P.; Petrovsky, Edouard A.; Novikov, Viktor V.
Contact information
Egorov, Denis E.:Siberian Federal University 79 Svobodny, Krasnoyarsk, 660041, Russia; Dovgun, Valery P.:Siberian Federal University 79 Svobodny, Krasnoyarsk, 660041, Russia; Petrovsky, Edouard A.:Siberian Federal University 79 Svobodny, Krasnoyarsk, 660041, Russia; Novikov, Viktor V.:Siberian Federal University 79 Svobodny, Krasnoyarsk, 660041, Russia
Keywords
nonlinear load; passive power filters; reactive power compensation
Abstract

The widespread use of adjustable speed drivers (ASD) in the petrochemical industry significantly increases the power-quality problems on the distribution network. Such problems can be reduced by adding passive harmonic filters in the distribution system. This paper presents a method for design passive power filters installed at the point of common coupling with ASD. The filter designed with the help of proposed method satisfies requirements of reactive power compensation and harmonic filtering. The design example illustrating the proposed approach is given. In the proposed example, more than 50 % harmonic reduction and full reactive power compensation are achieved

Pages
738-748
Paper at repository of SibFU
https://elib.sfu-kras.ru/handle/2311/13378

Creative Commons License This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License (CC BY-NC 4.0).